Lumens, lux and downlight calculator

Residential presets are suggestions.

CalculatorHow to useFrequently asked questions

Loading the calculator…

Residential presets are suggestions. Workplace targets reference EN 12464-1; CU and MF account for losses. The grid and uniform-cone lux estimate do not verify glare, uniformity or compliance; use fixture photometry.

How to use

  1. Enter the dimensions and electrical values.
  2. Adjust the assumptions to match your components.
  3. Read the result and check the technical limits below.

Formula and assumptions

Φ = E × A / (CU × MF); N ≥ Φ/Φ_spot; D = 2h × tan(θ/2); E_axis ≈ Φ / [2π(1 − cos(θ/2))d²].

Calculated example

Area
20 m²
Target illuminance
150 lx
Lumens per downlight
600 lm
Ceiling height
2.7 m
Working plane height
0.8 m
Utilization factor CU
60 %
Maintenance factor MF
80 %
Required luminous flux
6250 lm
Downlights in grid
12

Technical references

Frequently asked questions

How is this calculated?

Residential presets are suggestions. Workplace targets reference EN 12464-1; CU and MF account for losses. The grid and uniform-cone lux estimate do not verify glare, uniformity or compliance; use fixture photometry.